HH Series 6-10KVA 1-1 Phase

HH Series 6-10kVA Double-Conversion Online UPS adopts full digital control & ECO mode for high reliability and energy efficiency. Flexible battery expansion + multilingual LCD & SNMP option, expandable battery bank freely extends backup duration as your project demands.

Send Inquiry

Product Description

HH Series 6-10kVA Double-Conversion Online UPS adopts full digital control & ECO mode for high reliability and energy efficiency. Flexible battery expansion + multilingual LCD & SNMP option, expandable battery bank freely extends backup duration as your project demands.

 

 

Feature:

IGBT based rectifier true online double conversion

Microprocessor control optimizes reliability

DSP technology guarantees high performance

Pure sine wave output

Input power factor correction

Unity output power factor

Extremely wide input voltage window

50Hz/60Hz frequency converter mode

ECO and frequency operating voltage possibilities

Graphic LCD display with interactive multilingual user interface

Digital charger technology provides 0-10A charging current

Adjustable charging current/charging mode via LCD panel

Programmable output voltage

Cold start by battery without grid Input

Generator compatible

Extension slot for SNMP, potential-free contacts, remote panel

 

Parameters

Model HH6KS HH6KL HH10KS HH10KL
Rating 6kVA/6000W 10kVA/10000W
Input
Input system L+N+PE
Rated voltage 208/220/230/240VAC
Voltage range(110v-300v)

1. 110Vac~300Vac,

2. 110Vac~176Vac,

3. 280-300Vac, (power limited)

Frequency 50/60+6HZ (default), ±10HZ (can be set)
Power factor 0.99
Output
Output system L+N+PE
Power factor(PF) 1.0
Voltage 220V/110V BOTH
Wave Form Pure Sine Wave
Voltage harmonic distortion (rated input voltage. Rated input frequency)

≤3% (0~100% linear load)

≤5% (0~100% non-linear load)

Frequency 50 HZ/60 HZ ±0.05% HZ (Battery Model)

Inverter overload capability

(in normal mode, 25℃)

AC Mode:

30min@102%-110% Load

10min@110%-130% Load

30s@130%~150% Load

200ms@>150% Load

Battery Mode:

1min@102%-110% Load

10s@110%-130% Load

3s@130%~150% Load

200ms@>150% Load

Transfer time

AC mode switch to battery mode : 1-10ms

mains inverter mode switch to bypass mode : 4ms

Battery
Battery Voltage 192vdc
Charge Current(1-12A) 1A(DEFAULT) 1-10A settable
Qty. ×Volts. ×Capacity 16×12V×7Ah(16,20pcs optional)
Charging duration 90% of battery capacity in 8 hrs (standard type)
Interface
RS-232 Support: Windwos 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC
USB Windows FamIly & MAC
Intelligent slot(Optional) SNMP/AS400 Relay Card/RS485
Environmental parameters
Operating ambient temperature 0~40℃
Operating environment humidity 20%~95% (No condensation)
Storage temperature -15~60℃ (Battery: 0~40℃)
Altitude The altitude should not exceed 1000m, derating above1000m, up to 4000m (max), refer IEC62040
Noise ≤50db
Size And Weight
Dimensions (D*W*H) (mm) 460*190*615 365*188*320 460*190*615 395*190*325
Net weight (kg) 16 9.2 18.5 10

 