HHR Series 1–3kVA 1-1 Phase

HHR rack-mount online UPS is for space-saving cabinet deployment. Adopting double-conversion technology, it provides clean pure sine-wave power with high power factor up to 1.0, supporting ECO mode, flexible charging settings and multiple communication interfaces.

Send Inquiry

Product Description

HHR rack-mount online UPS is for space-saving cabinet deployment. Adopting double-conversion technology, it provides clean pure sine-wave power with high power factor up to 1.0, supporting ECO mode, flexible charging settings and multiple communication interfaces.

Feature:

IGBT based rectifier true online double conversion

Microprocessor control optimizes reliability

DSP technology guarantees high performance

Pure sine wave output

Input power factor correction

Unity output power factor

Extremely wide input voltage window

50Hz/60Hz frequency converter mode

ECO and frequency operating voltage possibilities

Graphic LCD display with interactive multilingual user interface

Digital charger technology provides 0-8A charging current

Adjustable charging current/charging mode via LCD panel

Programmable output voltage

Cold start by battery without grid Input

Generator compatible

Extension slot for SNMP, potential-free contacts, remote panel

 

Parameters

Model HHR1KS HHR1KL HHR2KS HHR2KL HHR3KS HHR3KL
Rating 1kVA/1000W 2kVA/2000W 3kVA/3000W
Input  
Input system L+N+PE
Rated voltage 208/220/230/240VAC
Voltage range

1. 110Vac~300Vac,

2. 110Vac~176Vac,

3. 280-300Vac, (power limited)

Frequency 50/60+6HZ (default), ±10HZ (can be set)
Power factor 0.99
Output  
Output system L+N+PE
Power factor 1.0
Voltage 208/220/230/240VAC
Wave Form Pure Sine Wave
Voltage harmonic distortion (rated input voltage. Rated input frequency)

≤3% (0~100% linear load)

≤5% (0~100% non-linear load)

Frequency 50 HZ/60 HZ ±0.05% HZ (Battery Model)
Inverter overload capability(in normal mode, 25℃)

AC Mode:

30min@102%-110% Load

10min@110%-130% Load

30s@130%~150% Load

200ms@>150% Load

Battery Mode:

1min@102%-110% Load

10s@110%-130% Load

3s@130%~150% Load

200ms@>150% Load

Transfer time

AC mode switch to battery mode : 0ms

mains inverter mode switch to bypass mode : 4ms

Battery  
Battery Voltage 24Vdc 36Vdc 48Vdc 72Vdc 72Vdc 96Vdc
Charge Current 1A(Default)1-5A settable
Interface  
RS-232 Support: Windwos 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC
USB Windows Famly & MAC
Intelligent slot(Optional) SNMP/AS400 Relay Card/RS485
Environmental parameters  
Operating ambient temperature 0~40℃
Operating environment humidity 20%~95% (No condensation)
Storage temperature -15~60℃ ( Battery : 0~40℃ )
Altitude The altitude should not exceed 1000m, derating above1000m, up to 4000m (max ), refer IEC62040
Noise ≤50db
Size And Weight  
Dimensions (D*W*H) (mm) 385x438x88(2U) 535x438x88(2U) 385x438x88(2U) 535x438x88(with handles)
Net weight (kg) 10.5 6.6 15.2 8.1 21.3 8.55