HM Series 60–600kVA 3-3 Phase

The HM series is a space-saving modular UPS solution with plug-and-play 20K/30K/50K power modules, it delivers PF up to 1.0. With N+X redundancy, protecting critical loads with flexible capacity expansion and stable clean power for data centers, industry and medical applications.

Send Inquiry

Product Description

The HM series is a space-saving modular UPS solution with plug-and-play 20K/30K/50K power modules, it delivers PF up to 1.0. With N+X redundancy, protecting critical loads with flexible capacity expansion and stable clean power for data centers, industry and medical applications.

 

Feature:

DSP full digital control technology

Input power factor up to 0.99

Parallel modules share the same battery pack

Advanced battery intelligent management technology

Module structure, UPS capacity can be changed based on loads

N+× redundancy

Efficiency of UPS is more than 96%, environmental protection

Friendly interface design of LCD

EPO function

Advanced battery management

3U frame, rack-mount

Microprocessor control, self-check, battery check by itself

Online static bypass, strong protection for overload and UPS fault

RS232 & SNMP for optional, to provide remote control management

intelligent temperature-controlled fan, long life and low noise

Power module 20K, 30K, 50K

 

Parameter

Model HM20-600KVA
CABINET CAPACITY 60KVA 80KVA 120KVA 200KVA 90KVA 120KVA 180KVA 210KVA 300KVA 400KVA 500KVA 600KVA
ONE POWER MODULE CAPACITY 20KVA/20KW 30KVA/30KW 50KVA/50KW
IMAX.POWER MODULE NO. 3 4 6 10 3 4 6 7 6 8 10 12
INPUT  
Nominal Voltage 3x380VAC/400VAC/415VAC (3Ph+N)
Voltage Range 305~478 VAC at 100% load;208~478VAC at<70% load
Nominal Frequency 50/60Hz(Auto Sensing)
Frequency Range 40Hz~70Hz
Power Factor >0.99@100% Load,>0.98@50%Load  
Harmonic Distortion (THDi) <3%@100% load
OUTPUT  
Nominal Voltage 3x380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation(Steady state) ≤±1% Typical (balanced load);≤±2% Typical (imbalanced load)
Nominal Frequency ZH09/09
Frequency Range(Synchronized) 46Hz~54Hz or 56Hz~64Hz
Overload Capability 1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for>150%
Harmonic Distortion ≤2% THD(Linear Load);≤4% THD(Non-linear Load)
Efficiency Up to 94.5%
BATTERY/CHARGER  
Nominal Voltage +/-216V(12V×36 pcs)
Maximum Voltage +/-240V(12V×40 pcs)
Minimum Voltage +/-192V(12V×32 pcs)
Float Charging Voltage 2.25V/Cell
Boost Charging Voltage 2.35V/Cell
Temperature Compensation Yes
Maximum Charging Current (Per Power Module) 6A 8A 8A
PHYSICAL  
Cabinet Dimension (DxWxH)mm 1100x514x763 1100x600x1475 1100x600x2010 1100x514x763 1100x600x1475 1100x600x2010 1065x600x2010
ENVIRONMENT  
Operating Temperature 0~40℃
Relative Humidity 0~95% non-condensing
Altitude <1000m for Nominal power
IP Protection IP 20
MANAGEMENT  
Smart RS-232/USB Supports Windows®2000/2003/XP/Vista/2008,Windows® 7/8/10,Linux and MAC